Counter · Timer Series ECT Series

Encoder Counter / RPM

A DIN-rail encoder counter. Counts encoder signals to display position, revolutions and RPM on a dual display, and fires relay and NPN outputs at the preset value. General sensor counting is also supported.

INICS Encoder Counter / RPM ECT1001 (ECT Series) — DIN-rail mount counter showing the dual 7-segment display (red count · green preset) and terminal block
10,000 RPM
RPM Range
6 DIGIT
Dual Display
10 KHZ
Max. Counting Speed
3 A
Relay Output

Key Features

FEATURE 01
Built for Encoders · 3 Input Models
Pick the model to match your encoder output. Connects directly to the full INICS encoder line-up — the SSI model pairs exclusively with INICS SSI encoders. TNV LINE DRIVER SSI
FEATURE 02
Counter + RPM Meter in One
One DIP switch turns the second display into an RPM meter — 10 to 10,000 RPM measured from the Z index at ±0.3% ±1 digit.
FEATURE 03
Dual 6-Digit Display
Red shows the live count (-99999 to 999999); green shows the preset or RPM — progress toward the target is visible at a glance.
FEATURE 04
Preset Match → Output & Auto-Reset
At the preset, relay (250VAC 3A) and NPN fire for 200 ms and the count auto-resets for the next cycle — ideal for cut-to-length and batch packaging.
FEATURE 05
General Sensor Mode
On the TNV model a DIP switch enables single-pulse counting from photo or proximity sensors — a quantity counter for lines without encoders.
FEATURE 06
Field-Friendly Design
DIN-rail or panel mount, key lock, front key and external reset. 10 kHz counting with 0.05 ms minimum pulse width. 95 × 110 × 43 mm.

System · Operation Flow

Count → Display → Output

From Encoder Counts to Control Signals

When the encoder's A/B/Z pulses arrive, the ECT counts them and shows the current value on the red display and the preset value on the green display. The moment the two match, the relay and NPN outputs fire and the count automatically restarts from zero.

  • A/B quadrature counting — counts up on CW and down on CCW rotation, reflecting direction.
  • Z signal = RPM — rotational speed is calculated from the period of the once-per-revolution Z pulse.
  • 200 ms one-shot output — on reaching the preset, relay and NPN outputs operate together for 200 ms to drive downstream equipment.
  • Auto-reset cycle — resets to zero immediately on reaching the preset, so repetitive processes run without interruption.